
I – Parameter definition
S900–II Configuration
Version 2.1
31
01T01506_1
25.11.99
PENDANT
PARAMETER Abbreviation Description Parameter
value
Corresponding function
0190
EXTINCTION
Time before screen goes into
stand–by in minutes
0 The screen does not go into stand–by.
1 –> 10 If you do not press a key during this time, the screen goes into stand–by.
Default value :
3
Possible value :
0 –> 10
Interaction with other parameters :
0191
TYP_BIP
Type of audible alarm 0 Intermittent.
1 Continuous.
Default value :
1
Possible value :
0 –> 1
Interaction with other parameters : 192, 193
0192
PERIOD_BIP
Length of audible alarm in
1/10 seconds
100 –> 500 Length of beeps if there is an alarm.
Default value :
100
Possible value :
100 –> 500
Interaction with other parameters : 191, 193
0193
RATIO_BIP
Cyclic report of the audible
alarm in percentage (%)
25 –> 75 Value of the cyclic report of the audible alarm.
T/2
T/2
T
RATIO_BIP = 50 % in this case.
Default value :
50
Possible value :
25 –> 75
Interaction with other parameters : 191, 192
Kommentare zu diesen Handbüchern