I – Parameter definition
S900–II Configuration
Version 2.1
8
01T01506_1
25.11.99
PARAMETER Abbreviation Description Parameter
value
Corresponding function
0004
CHG_PP_AUTO
Automatic program change 0 No automatic program change.
1 Automatic program change.
The code is positionned differently, depending on the status of
parameter 3 :
–> parameter 3 at 0, 1 or 2, the code number is given by the external inputs
(parameters 540 to 547) and the code validation by the input whose number
is given in parameter 511.
–> parameter 3 at 3 or 4, the code number is given by the supervisor system
(MotCod1, WORD 58) or WWORD 102 with Euromap 17.
The automatic program change is validated either :
by the 128 weighted bit of Mot Dial (WORD 43),
or by bit 33 (JBus and Euromap 17).
Default value :
0
Possible value :
0 –> 1
Interaction with other parameters : 3, 511, 540 –> 547
See the example of automatic program change in the S900–II Programming Manual Level 1.